Final | 12/27/2017 | 12/27/2017 | 12/27/2017 | P | PASS |
Rock A. Hudson
|
|
|
Call to meet // Jose Phone #: ###-#### Elevator permit for elevator installer not required due to job began prior to 7/1/17. All corrections complete. Final ok
|
Final | 11/21/2017 | 11/21/2017 | 11/21/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Contact Jose Phone #: ###-#### Inspection requested via web by Kevin Perez 300.4(E)- EMT raceways shall not be installed with in 1 1/2" of roof deck. If new or reused raceways they shall comply with current code cycle. 358.30- EMT shall be secured with in 3' of a box or conduit body.
|
Issue PAID IN FULL permit | | | 6/21/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/21/2017 | | DONE |
|
|
|
This permit was created on the web by Kevin Perez
|