Final | 8/2/2017 | 8/2/2017 | 8/2/2017 | P | PASS |
Mark Moncarr
|
|
|
Inspection requested via web by jamie berg No other work has been done. Closing out permit
|
Permanent Service | 8/1/2017 | 8/2/2017 | 8/2/2017 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by jamie berg p/s u/g n ok. Corrections needed to be made on work done by others. Centerline Elec corrected all items as needed. 250.8(5) Correct hardware was used to install ground lug. Previous hard ware was wood or sheetmetal screw. 110.14(A) Not all strands of conductor were installed under terminal. Strands were bent and smashed outside lug.
|
Permanent Service | 6/21/2017 | 6/21/2017 | 6/21/2017 | P | PASS |
Tom Saunders
|
|
|
200 amp service Phone #: ###-#### Inspection requested via web by jamie berg...
p/s u/g n ok
|
Issue PAID IN FULL permit | | | 6/21/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/21/2017 | | DONE |
|
|
|
This permit was created on the web by jamie berg
|