Final | 8/2/2017 | 8/2/2017 | 8/2/2017 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by jamie berg No other work has been done. Closing out permit.
|
Permanent Service | 8/1/2017 | 8/2/2017 | 8/2/2017 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by jamie berg p/s u/g n ok. Corrections needed to be made on work done by others. Centerline Elec corrected all items. 250.8(5) Self tapping sheetmetal screw was replaced with proper hardware. 110.14(A) Some strands of conductor were bent and smached outside of terminal.
|
Permanent Service | 6/21/2017 | 6/21/2017 | 6/21/2017 | P | PASS |
Tom Saunders
|
|
|
200 amp service Phone #: ###-#### Inspection requested via web by jamie berg...
p/s u/g n ok
|
Issue PAID IN FULL permit | | | 6/21/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/21/2017 | | DONE |
|
|
|
This permit was created on the web by jamie berg
|