Final | 10/31/2017 | 11/1/2017 | 11/1/2017 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Kevin Koomler Ok final. GFI functions properly for cover and lights.
|
Electrical Rough-In | 7/12/2017 | 7/13/2017 | 7/13/2017 | P | PASS |
Mark Moncarr
|
|
|
pool equipotential plane with 2ea metal fence posts on east side Phone #: ###-#### Inspection requested via web by Kevin Koomler Ok cover. Homeowner doesnt want to see the 2 fence post bonds visible in the pool area. 2 bonds are going to be stubbed under the fence and bonded on the front of the posts on the road side.
|
Electrical Rough-In | 6/27/2017 | 6/28/2017 | 6/28/2017 | A | PASS |
Mark Moncarr
|
|
|
Underground cover and bonding conductor home run Phone #: ###-#### Inspection requested via web by Kevin Koomler Ok cover. Metal chain links used for lifting purposes are embedded in fiberglass shell. Some concrete and pavers are going down around the border. Chains will not in contact with metal, and are going to be buried and not accessible.
|
Issue PAID IN FULL permit | | | 6/21/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/21/2017 | | DONE |
|
|
|
This permit was created on the web by Kevin Koomler
|