Final | 10/18/2017 | 10/19/2017 | 10/19/2017 | A | PASS |
Rock A. Hudson
|
|
|
code 4224 any ? call bill ###-#### Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
Final | 10/12/2017 | 10/13/2017 | 10/13/2017 | A | FAIL |
Rock A. Hudson
|
|
|
code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn 404.9, 406.6- All switch and receptacle outlet covers shall be installed. Several removed.
|
Rough-In Permanent Service | 7/5/2017 | 7/5/2017 | 7/5/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Corrections made rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 7/4/2017 | 7/5/2017 | 7/5/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn 110.3- Fireplace igniter wire shall be secured as to not be in contact with fireplace shell as per manufacurers instructions. 210.52- Tech room receptacle outlet shall be added to serve wall space with in 6' of left side of door. 210.52- Up family room shall have receptacle outlets added to serve wall space created by rail. 800.24- Communication wires shal be installed in a manner so they are not subject to physical damage. Upstairs hanging below ceiling.
|
Issue PAID IN FULL permit | | | 6/26/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/26/2017 | | DONE |
|
|
|
This permit was created on the web by Bob Glenn
|