Final | 10/5/2017 | 10/5/2017 | 10/5/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by steve cooper corrections made final ok
|
Final | 10/3/2017 | 10/4/2017 | 10/4/2017 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by steve cooper GFCI test on floor heat T stat not functioning. 210.11 C2 and C3. Laundry room 20 Branch circuit shall have no other outlets, Bathroom 20 branch circuit shall have no other outlets.
|
Rough-In Permanent Service | 7/20/2017 | 7/21/2017 | 7/21/2017 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by steve cooper Rough in ok cover p/s u/g n ok
|
Electrical Rough-In | 7/19/2017 | 7/20/2017 | 7/20/2017 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by steve cooper 110.14B Splices shall be made by identified devices. Smoke detector grounds. 300.4A1 Bored holes less than 1 1/4in need nail plates. ( Up bed wall next to laundry) 300.4 D Cables shall be supported 1 1/4in away from face of stud. Laundry counter recep, Up bath 2 gang.
|
Issue PAID IN FULL permit | | | 6/27/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/27/2017 | | DONE |
|
|
|
This permit was created on the web by steve cooper
|