Final | 1/4/2018 | 1/5/2018 | 1/5/2018 | A | PASS |
James Ady
|
|
|
Please call homeowner (number listed above) prior to arrival. Thanks Phone #: ###-#### Inspection requested via web by Kevin Perez Final ok
|
Electrical Rough-In | 7/21/2017 | 7/21/2017 | 7/21/2017 | P | PASS |
Rock A. Hudson
|
|
|
please contact homeowner prior to arrival. ###-#### Phone #: ###-#### Inspection requested via web by Kevin Perez Recept. missed to left of wet bar 3'6" wall between door and closet. Will be in by final. Rough in ok cover
|
Electrical Rough-In | 7/12/2017 | 7/13/2017 | 7/13/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Please call home owner prior to inspection for access. Thank you Phone #: ###-#### Inspection requested via web by Kevin Perez 210.52- In habitable rooms no space measured along floor line shall be more than 6' from a receptacle outlet. Dn bed and rec room. Wall wider than 2' near wet bar. 300.4- Protect cables where run thru holes that do not maintain 1 1/4" from framing surface. SER above main panel, several dn. 330.30- NM cables shall be secured 1 1/4" from framing surface.
|
Issue PAID IN FULL permit | | | 7/12/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/12/2017 | | DONE |
|
|
|
This permit was created on the web by Kevin Perez
|