Print Statement | | | 9/26/2017 | | DONE |
|
|
|
|
First Notice | 8/9/2017 | 8/9/2017 | 9/5/2017 | | DONE |
James Ady
|
|
|
This permit finaled on the web by Stacie Tasker
|
Final | 8/8/2017 | 8/9/2017 | 8/9/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Stacie Tasker Did not see sign off card onsite. Corrections made final ok
|
Final | 8/8/2017 | 8/8/2017 | 8/8/2017 | P | FAIL |
James Ady
|
|
|
Tobias is site contact. Phone #: ###-#### Inspection requested via web by Stacie Tasker 210.4 B all multiwire branch circuits shall have mean to simultaniously disc all ungrounded conductors. 210.8B5 All receps within 6ft of sink shall be GFCI protected. Dead receps in back storage room. All exhaust fan J Boxes shall have covers.
|
Electrical Rough-In | 8/8/2017 | 8/8/2017 | 8/8/2017 | P | PASS |
James Ady
|
|
|
Tobias is site contact. Phone #: ###-#### Inspection requested via web by Stacie Tasker Ceiling only ok to cover.
|
Final | 8/7/2017 | 8/8/2017 | 8/8/2017 | A | NR |
James Ady
|
|
|
Danny Phone #: ###-#### Not ready
|
Electrical Rough-In | 7/14/2017 | 7/17/2017 | 7/17/2017 | A | PASS |
James Ady
|
|
|
Tobias is the site contact. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Rough in walls only OK to cover
|
Issue PAID IN FULL permit | | | 7/14/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/14/2017 | | DONE |
|
|
|
This permit was created on the web by Stacie Tasker
|