Final | 10/24/2017 | 10/25/2017 | 10/25/2017 | A | PASS |
James Ady
|
|
|
Final - Code corrections fixed Phone #: ###-#### Inspection requested via web by Douglas Hackney Corrections made final ok
|
Final | 10/23/2017 | 10/24/2017 | 10/24/2017 | P | FAIL |
James Ady
|
|
|
New House Trim out / Final Phone #: ###-#### Inspection requested via web by Douglas Hackney Master bed T.V recep open Grnd, Sparkrings in Backsplash near butler pantry, Lock out dish/disp., Up laundry recep needs GFCI protected
|
Electrical Rough-In | 8/15/2017 | 8/15/2017 | 8/15/2017 | P | PASS |
James Ady
|
|
|
Fixed corrections. Phone #: ###-#### Inspection requested via web by Douglas Hackney Corrections made rough in ok p/s u/g n ok
|
Electrical Rough-In | 8/14/2017 | 8/14/2017 | 8/14/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Rough in Inspection Phone #: ###-#### Inspection requested via web by Douglas Hackney 300.4- MN cable shall be protected from damage where run thru bored holes that dor not maintain 1 1/4" from framing surface. 2 up lower plates under switch at top of stair and under bed window. 334.30 NM cable shall be secured within 12" of hall sconce. 422.11- 20 amp 120 volt circuit spec for furnace 15 amp installed. Soffits ok
|
Issue PAID IN FULL permit | | | 7/20/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/20/2017 | | DONE |
|
|
|
This permit was created on the web by Douglas Hackney
|