Final | 9/18/2017 | 9/18/2017 | 9/18/2017 | P | PASS |
Tom Saunders
|
|
|
Please contact Todd ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson....
corrections made...ok to final
|
Final | 9/15/2017 | 9/18/2017 | 9/18/2017 | A | FAIL |
Tom Saunders
|
|
|
first thing in morning...
1) GFI in breakroom has no power 2) outlet in breakroom needs GFI protection within 6' of sink 3) OCPD on A/Cs are too large...nameplate 4) A/C disconnects and panel need labelled to deferentiate each 5) disposal outlet needs completely installed to box 6) disposal outlet needs spark ring or extension added to bring flush....set back more than 1/4"
|
Final | 9/14/2017 | 9/15/2017 | 9/15/2017 | P | NR |
Tom Saunders
|
|
|
Please inspect for final as late in the afternoon as possible Phone #: ###-#### Inspection requested via web by Tracy Robertson...
scheduled for monday 18th 9:30-10:00
|
Electrical Rough-In | 9/14/2017 | 9/15/2017 | 9/15/2017 | A | PASS |
Tom Saunders
|
|
|
ceiling grid inspection Phone #: ###-#### Inspection requested via web by Tracy Robertson..
grid ok to cover
|
Electrical Rough-In | 9/11/2017 | 9/12/2017 | 9/12/2017 | P | PASS |
Tom Saunders
|
|
|
roughin for reception desk Phone #: ###-#### Inspection requested via web by Tracy Robertson...
ok to cover...front desk wall
|
Rough-In Permanent Service | 8/3/2017 | 8/4/2017 | 8/4/2017 | A | CANC |
Tom Saunders
|
|
|
call Todd if any issues please and thank you. And as early as possible please and thank you. Phone #: ###-#### Inspection requested via web by Tracy Robertson....
needed rough in only
|
Electrical Rough-In | 8/4/2017 | 8/4/2017 | 8/4/2017 | P | PASS |
Tom Saunders
|
|
|
call Todd if any issues please and thank you. And as early as possible please and thank you. Phone #: ###-#### Inspection requested via web by Tracy Robertson...
ok to cover walls and hard lid areas
|
Issue PAID IN FULL permit | | | 8/1/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/1/2017 | | DONE |
|
|
|
This permit was created on the web by Tracy Robertson
|
First Notice | 9/18/2017 | 9/18/2017 | | | |
Tom Saunders
|
|
|
|