Print Statement | | | 12/15/2017 | | DONE |
|
|
|
|
Final | 10/17/2017 | 10/18/2017 | 10/18/2017 | A | PASS |
Tom Saunders
|
|
|
It is open. If you have any questions please call Aaron ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan...corrections made...ok to final
|
Final | 10/16/2017 | 10/16/2017 | 10/16/2017 | P | FAIL |
Tom Saunders
|
|
|
It is open. If you have any questions please call Aaron ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan...1) service outlets for RTU have no power 2) LFNC needs supported-rooftop unit-356.30 3) GFI protection of all 120/240 volt outlets 210.8(B)(6) 4) breaker lockout or disconnect needs installed on water heater circuit
|
Permanent Service | 8/25/2017 | 8/25/2017 | 8/25/2017 | P | PASS |
Tom Saunders
|
|
|
If you have any questions please call Aaron ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan...
p/s u/g n ok
|
Rough-In Permanent Service | 8/18/2017 | 8/21/2017 | 8/21/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Should be open. If you have any questions please call Clay ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan See rough in for cover. 110.24- Available fault current shall be posted prior to permanent service inspection.
|
Electrical Rough-In | 8/21/2017 | 8/21/2017 | 8/21/2017 | P | PASS |
Rock A. Hudson
|
|
|
Should be open. If you have any questions please call Clay ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan Walls and hardlid rough in ok cover
|
Electrical Rough-In | 8/18/2017 | 8/21/2017 | 8/18/2017 | A | CANC |
Tom Saunders
|
|
|
Should be open. If you have any questions please call Clay ###-####. Thanks!! Phone #: ###-#### >> Inspection requested via web by Clay Morgan Inspection cancelled from web by: Clay Morgan
|
Issue PAID IN FULL permit | | | 8/7/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 8/7/2017 | | |
|
|
|
|
Application received | | | 8/7/2017 | | DONE |
|
|
|
This permit was created on the web by Clay Morgan
|
First Notice | 10/18/2017 | 10/18/2017 | | | |
Tom Saunders
|
|
|
|