Final | 12/14/2017 | 12/14/2017 | 12/14/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Stephanie Huston Corrections made final ok
|
Final | 12/13/2017 | 12/13/2017 | 12/13/2017 | P | PART |
James Ady
|
|
|
Temp final Phone #: ###-#### Inspection requested via web by Stephanie Huston Lock out on Front freezor and Coffee Machine, Sparkrings Both baths and Receiving receptacles,Water heater GFCI loose,Fridge receps dead, 24in pull box cover, Front weather proofs loose on siding. Partial final only ok
|
Final | 12/12/2017 | 12/12/2017 | 12/12/2017 | P | FAIL |
James Ady
|
|
|
Temp final for occupancy. Later if possible please Phone #: ###-#### Inspection requested via web by Stephanie Huston Customer shall provide access to all receptacles( Under desks, behind equipment)
|
Electrical Rough-In | 11/28/2017 | 11/28/2017 | 11/28/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Stephanie Huston Bonding only ok. EMT raceway for building steel jumper needs bonding bushing or replaced with PVC before final
|
Electrical Rough-In | 11/27/2017 | 11/27/2017 | 11/27/2017 | P | PASS |
James Ady
|
|
|
Service inspection, later if possible please Phone #: ###-#### Inspection requested via web by Stephanie Huston p/s u/g n ok
|
Electrical Rough-In | 11/21/2017 | 11/21/2017 | 11/21/2017 | P | PASS |
James Ady
|
|
|
Interior walls Later if possible Phone #: ###-#### Inspection requested via web by Stephanie Huston rough in ok Bath hard lids also ok to cover
|
Electrical Rough-In | 11/17/2017 | 11/17/2017 | 11/17/2017 | P | PASS |
James Ady
|
|
|
Later in afternoon if possible please, thanks Phone #: ###-#### Inspection requested via web by Stephanie Huston exterior walls only, outside lights and receps only rough in ok
|
Electrical Rough-In | 11/14/2017 | 11/14/2017 | 11/14/2017 | P | PASS |
James Ady
|
|
|
Partial wall inspection Phone #: ###-#### Inspection requested via web by Stephanie Huston North Exterior wall behind main service only ok to cover
|
Electrical Rough-In | 10/19/2017 | 10/19/2017 | 10/19/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Stephanie Huston NW corner of builing.Feeders and misc. coduits only ok to cover
|
Electrical Rough-In | 10/12/2017 | 10/12/2017 | 10/12/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Stephanie Huston Pump 2 and 6 Stub up to seal off only ok to cover
|
Electrical Rough-In | 10/11/2017 | 10/11/2017 | 10/11/2017 | P | PART |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Stephanie Huston Pump 1,3,4,5 ok to cover. Stub up to seal off only.
|
Electrical Rough-In | 10/3/2017 | 10/3/2017 | 10/3/2017 | P | PASS |
Rock A. Hudson
|
|
|
Rough in Underground from building to dispensers and tanks, verticals to be called in in future. Rough in ok cover
|
Electrical Rough-In | 10/3/2017 | 10/3/2017 | 10/3/2017 | P | CANC |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Stephanie Huston
|
Change Status to I | | | 10/3/2017 | | DONE |
|
|
|
Should not have been closed yet per James Ady
|
Electrical Rough-In | 8/29/2017 | 8/29/2017 | 8/29/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Stephanie Huston Underground from Service to fuel island and Com. Conduit to existing building ok to cover
|
Electrical Rough-In | 8/16/2017 | 8/16/2017 | 8/16/2017 | P | PASS |
James Ady
|
|
|
Ufer inspection Foreman Contact-Tom Hackman ###-#### Phone #: ###-#### Inspection requested via web by Stephanie Huston Footing already poured. Pictures were taken before pour.
|
Issue PAID IN FULL permit | | | 8/16/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 8/16/2017 | | |
|
|
|
|
Application received | | | 8/16/2017 | | DONE |
|
|
|
This permit was created on the web by Stephanie Huston
|
First Notice | 12/14/2017 | 12/14/2017 | | | |
James Ady
|
|
|
|
First Notice | 10/3/2017 | 10/3/2017 | | | |
James Ady
|
|
|
|