Final | 11/29/2017 | 11/30/2017 | 11/30/2017 | A | PASS |
Rock A. Hudson
|
|
|
Code 2010 Phone #: ###-#### Inspection requested via web by danny perrine Final ok
|
Final | 11/28/2017 | 11/29/2017 | 11/29/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Code 2010 Phone #: ###-#### Inspection requested via web by danny perrine 110.22- Furnace disconnect shall be so identified and on/off shall be identified. 422.12- Central heating appliance shall be on a dedicated branch circuit. When furnace breaker off opener receptacles went off.
422.12- Central heating appliance shall be on indvidual branch circuit. Garage door receptacles went off when furnace breaker turned off.
|
Rough-In Permanent Service | 8/23/2017 | 8/24/2017 | 8/24/2017 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by danny perrine p/s u/g n ok
|
Rough-In Permanent Service | 8/22/2017 | 8/23/2017 | 8/23/2017 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by danny perrine 210.52 A 2 1 Built in with countertop shall be considered wall space. Lt side of fireplace 314.16 Box fill. Office recep box with 5 14-2. 210.52 B 2 Small appliance circuits shall have no other receps. Net panel
|
Issue PAID IN FULL permit | | | 8/21/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/21/2017 | | DONE |
|
|
|
This permit was created on the web by danny perrine
|