Final | 1/31/2018 | 2/1/2018 | 1/31/2018 | A | PASS |
Mark Moncarr
|
|
|
###-#### John. Ok final. Corrections made. Looked at on 1/31/18. Recept in bath off kitchen was protected by a GFI in the mech. room. Contractor installed GFI in bath and blanked recept in mech. room.
|
Final | 1/31/2018 | 1/31/2018 | 1/31/2018 | P | CANC |
Mark Moncarr
|
|
|
John is on site and has corrections made Phone #: ###-#### Inspection requested via web by John Harvey Re-scheduled for 2/1/18
|
Final | 1/29/2018 | 1/29/2018 | 1/29/2018 | P | FAIL |
Mark Moncarr
|
|
|
Call john if any problems.
Key is hanging in the front left corner of the porch Phone #: ###-#### Inspection requested via web by John Harvey 1. Recept on corner of living/dining wall has open neutral. 2. Mstr bed not ARC fault protected. 3. GFI for bath off kitchen is located in basement mech room. Dedicated bath circuit cannot leave bath unless feeding another outlet in another bath. 4. Lockouts needed for appliances. Hood/DW/oven/micro.
|
Rough-In Permanent Service | 12/19/2017 | 12/20/2017 | 12/20/2017 | A | PASS |
Mark Moncarr
|
|
|
Conduit has been installed. Call john if any issues. Will be there by 9am Phone #: ###-#### Inspection requested via web by John Harvey p/s o/h n ok. Correction made. Conduit installed from meter main to basement panel.
|
Rough-In Permanent Service | 12/18/2017 | 12/19/2017 | 12/19/2017 | A | FAIL |
Mark Moncarr
|
|
|
Call john if any problems Phone #: ###-#### Inspection requested via web by John Harvey 2" conduit is not a full run to panel in basement. THHN is laying on floor of crawl space. Either continue conduit completely to basement panel, or pull SER to feed panel.
|
Electrical Rough-In | 8/23/2017 | 8/23/2017 | 8/23/2017 | A | PASS |
Mark Moncarr
|
|
|
Call john if any issues Phone #: ###-#### Inspection requested via web by John Harvey Ok cover. Corrections made.
|
Electrical Rough-In | 8/21/2017 | 8/22/2017 | 8/22/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Call John if any issues. Thanks. Phone #: ###-#### Inspection requested via web by John Harvey 210.52(A)- Dn bed all walls 24" or wider shall have a receptacle outlet installed. 300.4- Where NM cable is run thru bored or notched holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates. 334.30- NM cable shall be supported at intervals not to exceed 4 1/2' and be secured with in 12" of a box. Back can and kitchen boxes.
|