Final | 11/19/2017 | 11/20/2017 | 11/20/2017 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Ok final. Contractor took resposiblity for other work done by homeowner.
|
Final | 11/17/2017 | 11/27/2017 | 11/19/2017 | A | CANC |
Mark Moncarr
|
|
|
Inspection cancelled from web by: Barbara Szurgot
|
Final | 11/17/2017 | 11/17/2017 | 11/17/2017 | P | CANC |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot No body home
|
Final | 11/13/2017 | 11/14/2017 | 11/14/2017 | A | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot 110.25 Lockable disc for hard wired appliances 406 Tamper rsisitant receptacles in kitchen Open ground on recepts changed by homeowner have open ground and no GFCI protection, owner will need to pull permit to release contractor of the liability or contractor assume work in progress. Faceplates missing thru-out as well
|
Permanent Service | 9/5/2017 | 9/6/2017 | 9/6/2017 | P | PASS |
Mark Moncarr
|
|
|
OH service inspected so we can get Idaho Power back up. Phone #: ###-#### Inspection requested via web by Barbara Szurgot p/s o/h rec ok. Removed existing service, replaced with new.
|
Electrical Rough-In | 8/29/2017 | 8/30/2017 | 8/30/2017 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Ok cover
|
Issue PAID IN FULL permit | | | 8/29/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/29/2017 | | DONE |
|
|
|
This permit was created on the web by Barbara Szurgot
|