Final | 1/17/2018 | 1/17/2018 | 1/17/2018 | P | PASS |
Rock A. Hudson
|
|
|
Access is 7606* Phone #: ###-#### Inspection requested via web by Charles Davis Final ok
|
Electrical Rough-In | 11/28/2017 | 11/29/2017 | 11/29/2017 | A | PASS |
Eric Story
|
|
|
access code 7606* inspect living ; kitchen rough in Inspection requested via web by Charles Davis Kitchen and living room ok to cover
|
Electrical Rough-In | 10/16/2017 | 10/16/2017 | 10/16/2017 | A | PASS |
Eric Story
|
|
|
new addition, code 7606* Phone #: ###-#### Inspection requested via web by Charles Davis Back room addition only ok cover
|
Permanent Service | 9/4/2017 | 9/5/2017 | 9/5/2017 | A | PASS |
Rock A. Hudson
|
|
|
permanent service, concrete slab, bond in furnace room, access is lock box code 7606* Phone #: ###-#### Inspection requested via web by Charles Davis Metal underground water pipe located in back wall of utility room, shall remain accessible. p/s o/h n ok
|
Permanent Service | 8/30/2017 | 8/31/2017 | 8/31/2017 | A | FAIL |
Daryl DeGrange
|
|
|
service inspection only Phone #: ###-#### Inspection requested via web by Charles Davis NEC 250.50 Grounding systems shall all be bonded together- water pipe bond?
|
Issue PAID IN FULL permit | | | 8/30/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/30/2017 | | DONE |
|
|
|
This permit was created on the web by Charles Davis
|