Print Statement | | | 1/18/2018 | | DONE |
|
|
|
|
Final | 12/11/2017 | 12/11/2017 | 12/11/2017 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Card signed, Final ok..
|
Final | 12/7/2017 | 12/8/2017 | 12/8/2017 | A | PART |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Funiture on 1st floor only Temp final for furniture set only
|
Electrical Rough-In | 12/7/2017 | 12/8/2017 | 12/7/2017 | A | CANC |
James Ady
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
|
Final | 11/3/2017 | 11/3/2017 | 11/3/2017 | P | PART |
James Ady
|
|
|
2nd Floor Final Phone #: ###-#### Inspection requested via web by Kerri Hamilton 2nd floor only partial final furniture set only ok
|
Final | 11/2/2017 | 11/2/2017 | 11/2/2017 | P | PART |
James Ady
|
|
|
First floor only Phone #: ###-#### Inspection requested via web by Kerri Hamilton TV recep S entry 2 recep under stairs dead, N closet lights dead, Locker room receps Need GFCI protected, Updated Panel schedules. Furniture set ONLY Partial final ok
|
Electrical Rough-In | 10/31/2017 | 10/31/2017 | 10/31/2017 | A | CANC |
James Ady
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
|
Electrical Rough-In | 10/27/2017 | 10/27/2017 | 10/27/2017 | P | PASS |
James Ady
|
|
|
Later in the afternoon if possible please Phone #: ###-#### Inspection requested via web by Kerri Hamilton Ceiling only as marked on print ok to cover
|
Electrical Rough-In | 10/27/2017 | 10/27/2017 | 10/27/2017 | P | CANC |
James Ady
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
|
Electrical Rough-In | 10/26/2017 | 10/26/2017 | 10/26/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Areas marked on print, ceiling only ok to cover
|
Electrical Rough-In | 10/25/2017 | 10/26/2017 | 10/26/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Areas marked on print Ceiling only ok to cover
|
Electrical Rough-In | 10/25/2017 | 10/25/2017 | 10/25/2017 | P | PASS |
James Ady
|
|
|
Later in the afternoon would be appreciated if possible. Phone #: ###-#### Inspection requested via web by Kerri Hamilton Ceiling only as marked on print ok to cover
|
Electrical Rough-In | 10/24/2017 | 10/24/2017 | 10/24/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Ceiling only as marked on print ok to cover
|
Electrical Rough-In | 10/23/2017 | 10/23/2017 | 10/23/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Areas marked on print Ceiling only ok to cover
|
Electrical Rough-In | 10/19/2017 | 10/20/2017 | 10/20/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Area marked on print. Ceiling only ok to cover
|
Electrical Rough-In | 10/17/2017 | 10/18/2017 | 10/18/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 1st floor ceiling as marked on print ok to cover
|
Electrical Rough-In | 10/12/2017 | 10/12/2017 | 10/12/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
|
Electrical Rough-In | 9/28/2017 | 9/28/2017 | 9/28/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Underground for floor box and wall only
|
Electrical Rough-In | 9/22/2017 | 9/22/2017 | 9/22/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 5 offices 2nd floor only Walls only ok to cover.
|
Electrical Rough-In | 9/20/2017 | 9/21/2017 | 9/21/2017 | P | PASS |
James Ady
|
|
|
or Dustin at ###-#### Phone #: ###-#### Inspection requested via web by Kerri Hamilton Floor boxes in 3 meeting rooms Ground floor only.
|
Electrical Rough-In | 9/14/2017 | 9/15/2017 | 9/15/2017 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 1st floor, 1 wall yet to fir out, rest of 1st floor wall rough in ok cover
|
Electrical Rough-In | 9/14/2017 | 9/15/2017 | 9/14/2017 | A | CANC |
James Ady
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
|
Conference | 9/6/2017 | 9/7/2017 | 9/7/2017 | A | DONE |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Discussed the protection of electrical equipment where water and sprinkler piping previously installed above, The reusing of TC cable system from 1992 installation, and meeting room requirements. Drip pans shall be installed to protect electrical equipment. #10 TC cable shall be reused if compliant with articles 336 and 392.80. Collabrative rooms over 215 sq. ft. shall comply with 210.71 for floor receptacles and wall space requirements.
|
Issue PAID IN FULL permit | | | 9/6/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/6/2017 | | DONE |
|
|
|
This permit was created on the web by Kerri Hamilton
|
First Notice | 12/11/2017 | 12/11/2017 | | | |
Eric Story
|
|
|
|