Final | 1/31/2019 | 1/31/2019 | 1/31/2019 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk final ok
|
Rough-In Permanent Service | 9/8/2017 | 9/8/2017 | 9/8/2017 | P | PASS |
Rock A. Hudson
|
|
|
###-#### Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 9/7/2017 | 9/8/2017 | 9/8/2017 | A | PART |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk 110.3- Branch circuit for furnace shall be sized as per manufacturers instructions. 15 amp installed 20 amp and 12 ga. required. Contactor to check with manufacturer for correct circuit. 408.3(B)(2)- Barriers shall be in place at line side termination of panel board. OK insulate only
|
Issue PAID IN FULL permit | | | 9/7/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/7/2017 | | DONE |
|
|
|
This permit was created on the web by Alan Lusk
|