Final | 2/5/2018 | 2/5/2018 | 2/5/2018 | P | PASS |
Tom Saunders
|
|
|
Call Austin with questions. Phone #: ###-#### Inspection requested via web by Kurtis Boller...corrections made...ok to final
|
Final | 1/29/2018 | 1/29/2018 | 1/29/2018 | P | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Kurtis Boller... 1..outlets in pantry shall be on the small appliance circuit...210.52(B)(1)...verify 2..plate on switches in new bathroom needs replaced...move box..110.3 3..outlet in closet needs to be GFI protected..within 6' of shower...210.8(A) 4..all outlets and devices in bedrooms shall have AFCI protection...switch patio lights..210.12 5..outlets on island are not to code...210.52(C)(5)
|
Electrical Rough-In | 9/28/2017 | 10/3/2017 | 10/2/2017 | A | CANC |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Kurtis Boller...
inspection done 10/2/17 PM
|
Electrical Rough-In | 10/2/2017 | 10/2/2017 | 10/2/2017 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Kurtis Boller...rough ok to cover..check at final furnace homerun and 2 outlets under tv outlets in master bed and sitting area
|
Issue PAID IN FULL permit | | | 9/8/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/8/2017 | | DONE |
|
|
|
This permit was created on the web by Kurtis Boller
|