First Notice | 9/18/2019 | 9/18/2019 | 9/20/2019 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Debby Pierce
|
Final | 9/18/2019 | 9/18/2019 | 9/18/2019 | P | PASS |
Rock A. Hudson
|
|
|
Duane Oreilly contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Correction made. Final ok
|
Final | 9/5/2019 | 9/6/2019 | 9/6/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Duane Oreilly is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce 314.25- All boxes shall have covers. 330.30- MN cable shall be secured with in 12" of a box. Building permit noted some areas of grid being replaced. History of inspections show no grid inspection performed. Just in from front door looked up and noticed 2 open boxes and KO seals needed and unsecured MC cable. Will need to meet contact on site with ladder to check areas above grid.
|
ELE-Aging Inspection | 9/5/2019 | 9/5/2019 | 9/5/2019 | | FAIL |
Rock A. Hudson
|
|
|
Called left message with contact. I remember job would be done in phases so might be still under construction
|
Electrical Rough-In | 1/31/2018 | 2/1/2018 | 2/1/2018 | P | PASS |
Rock A. Hudson
|
|
|
Terry Cushing is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Entry 1/2 wall and drinking fountain wall rough in ok cover
|
Electrical Rough-In | 1/23/2018 | 1/24/2018 | 1/24/2018 | A | CANC |
Rock A. Hudson
|
|
|
Terry Cushing is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Called contact. No new work done yet. Valuation corrected. Thank You
|
Electrical Rough-In | 1/23/2018 | 1/23/2018 | 1/23/2018 | P | PART |
Rock A. Hudson
|
|
|
Terry Cushing is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Contractor to increase valuation, future inspections may be delayed if not corrected. Walls noted on contractor print, east office walls, walls with display sconces, south wall near drinking fountain, and fireplace walls and hardlids noted only rough in ok cover
|
Electrical Rough-In | 11/16/2017 | 11/16/2017 | 11/16/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Jason Wells is contact on this project at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce NO BLD permit found. Spoke with rep and stated architect still working on plans. Unable to inspect due to BLD permit issue. 330.30- MC shall be secured with in 12" of a box. 362.30- ENT shall be secured with in 3' of a box. Verbal with contact
|
Electrical Rough-In | 9/20/2017 | 9/21/2017 | 9/21/2017 | A | PASS |
Rock A. Hudson
|
|
|
Terry Cushing is the contact on site ###-#### Phone #: ###-#### Inspection requested via web by Debby Pierce Future work to be permited when building permit is pulled. Floor receptacles only rough in ok cover
|
Issue PAID IN FULL permit | | | 9/20/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 9/20/2017 | | |
|
|
|
|
Application received | | | 9/20/2017 | | DONE |
|
|
|
This permit was created on the web by Debby Pierce
|