Final | 9/26/2017 | 9/27/2017 | 9/27/2017 | A | PASS |
Mark Moncarr
|
|
|
Requesting inspection after 10AM, if possible please
:Please call Tate with any questions ###-####
Thanks and have a great day! Phone #: ###-#### Inspection requested via web by JENNY EMEL Ok final.
|
Final | 9/27/2017 | 9/27/2017 | 9/27/2017 | P | CANC |
Mark Moncarr
|
|
|
Thank you and have a nice day! Phone #: ###-#### >> Inspection requested via web by JENNY EMEL Inspection cancelled from web by: JENNY EMEL
|
Conference | 9/21/2017 | 9/21/2017 | 9/21/2017 | P | DONE |
Rock A. Hudson
|
|
|
Please contact Tate Borstelman @ ###-####
Have a lovely day and THANK YOU!!! Phone #: ###-#### Inspection requested via web by JENNY EMEL Discussed equipment grounding of new watt meter being installed for new solar array system. Single bonding point for grounded conductor shall remain in place, at watt meter location grounded conductor shall splice thru meter with grounding conductor to terminate at lugs and bond meter can. Grounded conductor shall not be connected to noncurrent carryiing metal parts on load side of service. If connection to grounded conductor needed for watt meter a tap shall be supplied off isolated connection of grounded conductor.
|
Issue PAID IN FULL permit | | | 9/21/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/21/2017 | | DONE |
|
|
|
This permit was created on the web by JENNY EMEL
|