Final | 1/12/2018 | 1/12/2018 | 1/12/2018 | P | PASS |
Eric Story
|
|
|
Unit 5144 Phone #: ###-#### Inspection requested via web by David Nelson Correction fixed final ok
|
Final | 1/12/2018 | 1/12/2018 | 1/12/2018 | A | FAIL |
Eric Story
|
|
|
406 Receptacle replacement with open ground shall be GFCI protected and identified as open ground and Ground fault protected. Rest of unit check out fine
|
Conference | 10/9/2017 | 10/10/2017 | 10/10/2017 | A | DONE |
Rock A. Hudson
|
|
|
Would like to meet inspector on site, please call with ETA ###-####. Thank you. Phone #: ###-#### Inspection requested via web by David Nelson Discussed required wiring of fire damaged appartments. All wiring damaged by heat or water shall be replaced as needed. Where units have totally opened up walls and ceilings, wiring shall be replaced to all new codes. Areas with only smoke damage not required to be brought up to code due to wiring not being replaced. BCC 4-05-32 Code violations not to be retained. City ordinance requires code violations to be repaired even if damage is not present. Found paddle fans installed on boxes not rated for fans and microwaves installed on general lighting circuits with splice buried in walls. If fans to remain listed boxes shall be installed. Circuits shall be added for microwaves or hoods shall be istalled to eliminate overloads. If additional life safety code violations are found during rebuild they shall be repaired.
|
Issue PAID IN FULL permit | | | 10/9/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/9/2017 | | DONE |
|
|
|
This permit was created on the web by David Nelson
|
First Notice | 1/12/2018 | 1/12/2018 | | | |
Eric Story
|
|
|
|