Final | 1/20/2018 | 1/22/2018 | 1/22/2018 | A | PASS |
James Ady
|
|
|
garage code 1905, corrections have been fixed Phone #: ###-#### Inspection requested via web by kevin blackmon corrections made final ok
|
Final | 1/18/2018 | 1/19/2018 | 1/19/2018 | P | FAIL |
James Ady
|
|
|
garage code 1905 Phone #: ###-#### Inspection requested via web by kevin blackmon 210.8A7 receps within 6ft of sink shall be GFCI protected. 210.52C1 Receps shall be installed so that no point measured along wall line is more than 24in from recep. 314.20 Boxes set back more than 1/4in shall have extension ring
|
Rough-In Permanent Service | 10/19/2017 | 10/20/2017 | 10/20/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by kevin blackmon Rough in ok to cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 10/12/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/12/2017 | | DONE |
|
|
|
This permit was created on the web by kevin blackmon
|