Final | 1/17/2018 | 1/17/2018 | 1/17/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez Final ok
|
Final | 1/3/2018 | 1/3/2018 | 1/3/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez BCC 4-05-17(C)- It shall be unlawful to impede inspector. House staged prior to inspectoin. Unable to check all receptacles. 110.3- Devices shall be wired as per instructions. Stair 3 way switch miswire. Master bath GFCI will not hold for test. 210.8- Washer receptacle located with in 6' of a sink shl have GFCI protection. Recetpacles located in unfinished basement room shall have GFCI protection. 210.12- Master bed and down bed shall have AFCI protection. Breakers labeled GFCI only. 210.52(B)- Receptacle for island counter top shall be located with in 6" of overhang. 210.52(D)- Required bathroom receptacles shall be located adjacent to each basin. Add additional for 2nd down bath basin. 210.70- Luminaire shall be installed at each door with exterior access. Basement patio light needs installed. 422.30- Water heater shall have a disconnecting means with in sight of appliance. 110.25 lockout acceptable.
|
Permanent Service | 12/18/2017 | 12/18/2017 | 12/18/2017 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez p/s u/g n ok
|
Electrical Rough-In | 12/13/2017 | 12/13/2017 | 12/13/2017 | P | PASS |
Rock A. Hudson
|
|
|
Underground Inspection for service Phone #: ###-#### Inspection requested via web by Kevin Perez 110.3- Expansion joints shall be installed as per manufacturers instructions. Installed upside down. Bell end shall be positioned as to not collect moisture or dirt. 225.32- A disconnecting means shall be provided on house at a readily accessible location either outside on inside at nearest point of entrance of conductors. expansion joists located above grade. Verbal with Tom on corrections for final. Underground rough in ok cover
|
Electrical Rough-In | 11/3/2017 | 11/3/2017 | 11/3/2017 | P | PASS |
Rock A. Hudson
|
|
|
Rough in for detached garage. Phone #: ###-#### Inspection requested via web by Kevin Perez Rough in ok cover
|
Electrical Rough-In | 11/1/2017 | 11/1/2017 | 11/1/2017 | P | PASS |
Rock A. Hudson
|
|
|
Finish rough-in inspection for basement Phone #: ###-#### Inspection requested via web by Kevin Perez Basement rough in ok cover
|
Electrical Rough-In | 10/25/2017 | 10/27/2017 | 10/27/2017 | P | PART |
Rock A. Hudson
|
|
|
Please call Tom with any questions. Phone #: ###-#### Inspection requested via web by Kevin Perez Must allow time to move home runs to basement for new panel location. Main floor only rough in ok cover
|
Temporary Service | 10/13/2017 | 10/13/2017 | 10/13/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez Temp service require a seperate permit. When a temp service is passed permit automatically finals
|
Issue PAID IN FULL permit | | | 10/13/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/13/2017 | | DONE |
|
|
|
This permit was created on the web by Kevin Perez
|