Final | 1/3/2018 | 1/3/2018 | 1/3/2018 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Ben Archibald correction made final ok
|
Final | 1/1/2018 | 1/2/2018 | 1/2/2018 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Ben Archibald 210.52 All garage receps shall be GFCI protected. (Back wall) 210.70A(2)(2) Garage mandoor shall have exterior light.( May be barried wire) 422.31. All permanently installed appliances shall have disc. means.( Dish washer)
|
Electrical Rough-In | 12/10/2017 | 12/11/2017 | 12/11/2017 | A | PASS |
Rock A. Hudson
|
|
|
Heated tile floor inspection in bathrooms Phone #: ###-#### Inspection requested via web by Ben Archibald Floor heat 2 bathrooms rough in ok cover
|
Electrical Rough-In | 10/17/2017 | 10/18/2017 | 10/18/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Ben Archibald Whole house, minus garage, rough in ok to cover
|
Issue PAID IN FULL permit | | | 10/17/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/17/2017 | | DONE |
|
|
|
This permit was created on the web by Ben Archibald
|