Final | 10/31/2017 | 10/31/2017 | 10/31/2017 | P | PASS |
Mark Moncarr
|
|
|
Bonding Phone #: ###-#### Inspection requested via web by Eric White Ok cover. Perimeter bond at 4" depth. Pockets for diving board on W side, ladder on S side and handrail on E side all bonded with UL listed PVC bonding pockets.
|
Conference | 10/24/2017 | 10/25/2017 | 10/25/2017 | A | DONE |
Mark Moncarr
|
|
|
Project is in the back yard. Phone #: ###-#### Inspection requested via web by Eric White Discussed EQ plane and main bond from pool equipt. Also discussed bonding diving board and ladder.
|
Issue PAID IN FULL permit | | | 10/24/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/24/2017 | | DONE |
|
|
|
This permit was created on the web by Eric White
|