Final | 11/1/2017 | 11/2/2017 | 11/2/2017 | A | PASS |
Mark Moncarr
|
|
|
Contact: Jason Noble Phone #: ###-#### Inspection requested via web by Deb Gooden Ok final. Talked to contractor, they are going to install a short piece of unistrut for mast on detached garage. Also, a small pool is going to be installed within 5 ft of underground feeding house. 680.11 allows this as long as the installation is in rigid metal, intermediate metal, or rigid PVC. 680.10 was deleted from previous 2014 code which required wiring not associated with the pool to be atleast 5 ft away. It is now based on 300.5 cover requirements.
|
Permanent Service | 10/27/2017 | 10/30/2017 | 10/30/2017 | A | PASS |
Mark Moncarr
|
|
|
Contact: Jason Noble Phone #: ###-#### Inspection requested via web by Deb Gooden p/s o/h rec ok
|
Permanent Service | 10/26/2017 | 10/30/2017 | 10/27/2017 | P | CANC |
Mark Moncarr
|
|
|
Contact: Jason Noble Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
|
Electrical Rough-In | 10/26/2017 | 10/26/2017 | 10/26/2017 | P | PASS |
Mark Moncarr
|
|
|
Contact Jason Noble - underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden OK cover. 2 grd rods in trench 6' apart at a depth of 36"
|
Issue PAID IN FULL permit | | | 10/26/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/26/2017 | | DONE |
|
|
|
This permit was created on the web by Deb Gooden
|