Temporary Service | 11/8/2017 | 11/9/2017 | 11/9/2017 | A | PASS |
Mark Moncarr
|
|
|
Temp Pole inspection Phone #: ###-#### Inspection requested via web by Kevin Perez t/s o/h n ok. Mountain Power talked with IDP, and there 4x6 temp pole was ok to use.
|
Temporary Service | 11/6/2017 | 11/7/2017 | 11/7/2017 | P | FAIL |
Mark Moncarr
|
|
|
Temp Power Pole inspection Phone #: ###-#### Inspection requested via web by Kevin Perez Temp o/h service is only about 9' from weather head to grade. Temp power will be coming from alley way. Temp pole will need to be atleast 15'. Told contractor to contact IDP to get a definate answer on the height.
|
Issue PAID IN FULL permit | | | 11/6/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/6/2017 | | DONE |
|
|
|
This permit was created on the web by Kevin Perez
|