Temporary Service | 11/27/2017 | 11/27/2017 | 11/27/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall 250.53(G)- Ground rod shall be minimum of 8' in length and shall be flush with grade. Rod cut off and is above grade. 312.10(B)- Enclosure shall be of adequate strength. Meter and panel covers missing screws. 590.6(B)- All receptacle outets being used for temp power shall have GFCI protection. 250 GFI present but wiring connected to standard breaker.
|