Temporary Service | 12/6/2017 | 12/7/2017 | 12/7/2017 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall t/s u/g n ok
|
Temporary Service | 11/27/2017 | 11/27/2017 | 11/27/2017 | P | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall 110.12B Internal areas shall be free from debris.
|
Issue PAID IN FULL permit | | | 11/15/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/15/2017 | | DONE |
|
|
|
This permit was created on the web by Tracy Robertson
|
First Notice | 12/7/2017 | 12/7/2017 | | | |
Rock A. Hudson
|
|
|
|