Print Statement | | | 5/18/2018 | | DONE |
|
|
|
|
Final | 1/25/2018 | 1/26/2018 | 1/26/2018 | A | PASS |
Rock A. Hudson
|
|
|
Call Pierce for final inspection of phase 7. As early as possible please.
Thanks Phone #: ###-#### Inspection requested via web by Rafael Castillo Final ok
|
Electrical Rough-In | 1/19/2018 | 1/19/2018 | 1/19/2018 | A | PASS |
Rock A. Hudson
|
|
|
Call Pierce for grid ceiling inspection of 3 northern most bathrooms. Early AM preferred due to event being held in Boise Centre. Thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo 4 northern bathrooms grid rough in ok cover
|
Electrical Rough-In | 1/12/2018 | 1/12/2018 | 1/12/2018 | P | PART |
Rock A. Hudson
|
|
|
314.16- Boxes shall have free space for all conductors enclosed in box. Displays beside each ball room entrance have 7.5 cubic in. need 11.25 minimum. Contact stated these are existing boxes however only 1 has a receptacle installed at time of inspection. 4-05-32- Code violation not to be retained. Grid at each entrance rough in ok cover
|
Electrical Rough-In | 1/9/2018 | 1/10/2018 | 1/10/2018 | A | PASS |
Rock A. Hudson
|
|
|
Call Pierce for inspection of can light housings in soffits in bathrooms. Late AM preferred. Thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo 4 bathrooms soffit cans rough in ok cover
|
Electrical Rough-In | 12/28/2017 | 1/3/2018 | 1/3/2018 | A | PASS |
Rock A. Hudson
|
|
|
Call Rafael for inspection of new framed walls outside of the grand ballroom. Please call 30 minutes in advance to ensure access to the building. Thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo Main ballroom entrance wall rough in ok cover.
|
Issue PAID IN FULL permit | | | 11/15/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/15/2017 | | DONE |
|
|
|
This permit was created on the web by Cathy Duchek
|