Print Statement | | | 11/23/2018 | | DONE |
|
|
|
Sent 1st late notice
|
Print Statement | | | 7/17/2018 | | DONE |
|
|
|
|
Final | 1/28/2018 | 1/29/2018 | 1/29/2018 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Steve Craig...corrections made...ok to final
|
Final | 1/24/2018 | 1/25/2018 | 1/25/2018 | P | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Steve Craig....1) all outlets need completed with power-outlets below counter have no power, unable to verify GFI protection 2) OCPD on hot wells are too large-15A max on nameplate 3) roof top units need labelled 4) cooler cases need finished, outlets need mounted to proper cover plates-2 of them
|
Final | 1/23/2018 | 1/24/2018 | 1/24/2018 | A | FAIL |
Tom Saunders
|
|
|
Final inspection for kitchen addition in existing building Inspection requested via web by Steve Craig...miscellaneous equipment not hooked up need finished, outlets no power, outlet needs moved...cannot modify plate, breakers not on in panel...reason?, breaker lockouts need installed on ocpd of hard wired appliances
|
Electrical Rough-In | 1/19/2018 | 1/19/2018 | 1/19/2018 | P | PASS |
Mark Moncarr
|
|
|
Ceiling cover inspection in kitchen and prep room Phone #: ###-#### Inspection requested via web by Steve Craig Ok cover kitch and prep area ceilings.
|
Electrical Rough-In | 12/17/2017 | 12/18/2017 | 12/18/2017 | A | PASS |
Rock A. Hudson
|
|
|
call one half hour before inspection to ensure building is unlocked Phone #: ###-#### Inspection requested via web by Steve Craig Wall rough in ok cover
|
Electrical Rough-In | 12/14/2017 | 12/15/2017 | 12/15/2017 | A | FAIL |
Daryl DeGrange
|
|
|
Call 30 minutes prior to inspection so I can make sure the door is unlocked inspect new steel stud walls for cover Phone #: ###-#### Inspection requested via web by Steve Craig NEC 330.12 (1) MC cable shall not be installed where subject to physical damage. Along inside 2x4 steel stud door frame. 300.5 shall not install MC cable within 1 1/4 of edge of framing member
|
Electrical Rough-In | 12/4/2017 | 12/4/2017 | 12/4/2017 | P | PASS |
Tom Saunders
|
|
|
Rough in of 5 floor boxes before concrete por Phone #: ###-#### Inspection requested via web by Steve Craig...ok to cover
|
Issue PAID IN FULL permit | | | 12/3/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/3/2017 | | DONE |
|
|
|
This permit was created on the web by Steve Craig
|
First Notice | 1/29/2018 | 1/29/2018 | | | |
Tom Saunders
|
|
|
|