First Notice | 6/6/2018 | 6/6/2018 | 2/28/2019 | | DONE |
Rock A. Hudson
|
|
|
|
Final | 6/5/2018 | 6/6/2018 | 6/6/2018 | A | PASS |
Rock A. Hudson
|
|
|
Matt. Call prior to heading to site. Phone #: ###-#### Inspection requested via web by Sean DeLacy No Card posted. Final ok
|
Final | 5/29/2018 | 5/30/2018 | 5/30/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Matt. Call prior to heading to the site. Phone #: ###-#### Inspection requested via web by Sean DeLacy 210.8(B)- All receptacle outlets located with in 6' of a sink shall have GFCI protection. Pop counter. 408.7- Unused openings shall be closed by approved means. High voltage panel needs breaker blanks. 426.28- Equipment shall be protected by an equipment protection device. EPD on heat tape circuit.
|
Electrical Rough-In | 4/2/2018 | 4/4/2018 | 4/4/2018 | A | PASS |
Rock A. Hudson
|
|
|
Matt. Ceiling cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy 210.62- Any window that can be used for advertising shall have show window receptacles installed. Grid rough in ok cover
|
Electrical Rough-In | 1/3/2018 | 1/5/2018 | 1/5/2018 | A | PASS |
Eric Story
|
|
|
Wall Cover. Contact is Matt Phone #: ###-#### Inspection requested via web by Buster Bowen Walls only and hard lids in bath/storage rooms ok to cover
|
Issue PAID IN FULL permit | | | 12/13/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/13/2017 | | DONE |
|
|
|
This permit was created on the web by Sean DeLacy
|