Final | 3/13/2018 | 3/14/2018 | 3/14/2018 | A | PASS |
Rock A. Hudson
|
|
|
Final for Basement. Please call Travis with Vertical Construction when on your way or to schedule a time so he can let you in. ###-#### Phone #: ###-#### Inspection requested via web by Cyndi Dale Final ok
|
Final | 3/13/2018 | 3/13/2018 | 3/13/2018 | P | NH |
Rock A. Hudson
|
|
|
Final inspection in the basement Phone #: ###-#### Inspection requested via web by Cyndi Dale Unit locked contact unable to reach anyone for access. Will reschedule.
|
Electrical Rough-In | 12/15/2017 | 12/15/2017 | 12/15/2017 | P | PASS |
Rock A. Hudson
|
|
|
re-inspection of basement rough in. Phone #: ###-#### Inspection requested via web by Cyndi Dale Accesses marked but not framed in. Have pic of area between center columns. Walls and ceilings rough in ok cover
|
Electrical Rough-In | 12/15/2017 | 12/15/2017 | 12/15/2017 | A | CANC |
Rock A. Hudson
|
|
|
re-inspect of basement rough-in Phone #: ###-#### >> Inspection requested via web by Cyndi Dale Inspection cancelled from web by: Cyndi Dale
|
Electrical Rough-In | 12/13/2017 | 12/14/2017 | 12/14/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Call Chase if needed - ###-####. Basement rough-in only Phone #: ###-#### Inspection requested via web by Cyndi Dale 300.15- All wiring shall terminate in a box. Open wiring out of flex, MC in soffit area. All covers shall be accessible after installation. 314.25- All boxes shall have covers installed. Several boxes with wiring hanging out in soffit area. 330.12- MC shall not be installed where subject to damage. MC hanging below soffit and below soffit framing member.
|
Issue PAID IN FULL permit | | | 12/13/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 12/13/2017 | | |
|
|
|
|
Application received | | | 12/13/2017 | | DONE |
|
|
|
This permit was created on the web by Cyndi Dale
|
First Notice | 3/14/2018 | 3/14/2018 | | | |
Rock A. Hudson
|
|
|
|