Final | 3/1/2018 | 3/2/2018 | 3/2/2018 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by cris flores Final ok
|
Final | 2/9/2018 | 2/9/2018 | 2/9/2018 | P | CANC |
James Ady
|
|
|
Phone #: ###-#### >> Inspection requested via web by cris flores Inspection cancelled from web by: cris flores
|
Electrical Rough-In | 12/14/2017 | 12/15/2017 | 12/15/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by cris flores corrections made rough in ok
|
Electrical Rough-In | 12/14/2017 | 12/14/2017 | 12/14/2017 | P | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by cris flores 314.27. Boxes at ceiling paddle fan locations shall be listed for paddle fan support. 210.52. A 2. Wall space. Receps shall not be more than 12ft apart.
|
Issue PAID IN FULL permit | | | 12/14/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/14/2017 | | DONE |
|
|
|
This permit was created on the web by cris flores
|