Final | 4/3/2018 | 4/4/2018 | 4/4/2018 | A | PASS |
Rock A. Hudson
|
|
|
Garage code 8624 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|
Final | 4/2/2018 | 4/3/2018 | 4/3/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Garage Code 8624 Phone #: ###-#### Inspection requested via web by Darryn Coburn 314.16- Boxes shall be of an approved size for free conductor space. Box and end of peninsula 8 cu. in. with 11.25 cu in. installed. 422.30- A means shall be provided to disconnect appliances from power. Hood, microwave. Lockout acceptable.
|
Rough-In Permanent Service | 12/28/2017 | 12/29/2017 | 12/29/2017 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 12/20/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/20/2017 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|