Final | 6/27/2018 | 6/28/2018 | 6/28/2018 | A | PASS |
James Ady
|
|
|
Shane Phone #: ###-#### Final ok
|
Final | 6/26/2018 | 6/27/2018 | 6/27/2018 | P | PART |
James Ady
|
|
|
Shane Phone #: ###-#### Check scale receps. 3 banks of lights and gutter wires 2in ko seal.
|
Final | 6/21/2018 | 6/22/2018 | 6/22/2018 | A | FAIL |
Daryl DeGrange
|
|
|
Per AJS - need ok for TCO on Fedex bldg Phone #: ###-#### Not all conduit bodies have cover plates. Article 344.30(B)(3) Exposed vertical risers from industrial machinery or fixed equipment shall be permitted to be supported at intervals not exceeding 6 m (20 ft) if the conduit is made up with threaded couplings, the conduit is supported and securely fastened at the top and bottom of the riser, and no other means of intermediate support is readily available.
|
Final | 6/18/2018 | 6/20/2018 | 6/20/2018 | A | FAIL |
Daryl DeGrange
|
|
|
Trent Phone #: ###-#### Not all corrections complete.
|
Final | 6/5/2018 | 6/6/2018 | 6/6/2018 | A | NR |
James Ady
|
|
|
MCP01-control -Shane Phone #: ###-#### Not ready. Need to see conveyors opperate, all condulet covers must be in place.
|
Electrical Rough-In | 6/6/2018 | 6/6/2018 | 6/6/2018 | A | PASS |
James Ady
|
|
|
MCP01-control -Shane Phone #: ###-#### MCP 1 and MCP 2. Internal Wire terminations and Disc only. OK
|
Electrical Rough-In | 5/18/2018 | 5/18/2018 | 5/18/2018 | P | PASS |
James Ady
|
|
|
Trent Phone #: ###-#### bushings installed in raceways for MCP
|
Rough-In Permanent Service | 4/27/2018 | 4/30/2018 | 5/1/2018 | P | CANC |
James Ady
|
|
|
Trent-insp to get service to controll cabanets Phone #: ###-####
|
Electrical Rough-In | 4/30/2018 | 4/30/2018 | 4/30/2018 | P | FAIL |
James Ady
|
|
|
Trent-insp to get service to controll cabanets Phone #: ###-#### 300.4G Where raceways containing #4 or larger, shall be protected by an identified insulated fitting. (Feeders to MCP)
|
Issue PAID IN FULL permit | | | 12/22/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 12/22/2017 | | |
|
|
|
|
Application received | | | 12/22/2017 | | DONE |
|
|
|
This permit was created on the web by Amber Bishop
|
First Notice | 6/28/2018 | 6/28/2018 | | | |
James Ady
|
|
|
|