Final | 2/21/2018 | 2/21/2018 | 2/21/2018 | P | PASS |
Mark Moncarr
|
|
|
1331 Phone #: ###-#### Inspection requested via web by Neal Rumsey Ok final. Corrections made.
|
Final | 2/20/2018 | 2/20/2018 | 2/20/2018 | P | FAIL |
Tom Saunders
|
|
|
Code 1331 Phone #: ###-#### Inspection requested via web by Neal Rumsey
1..outlet in kitchen has hot/neutral reversed..frig 2. plate missing off outlet..living rm 3. breaker on A/C circuit is too small for demand load as per nameplate
|
Rough-In Permanent Service | 12/28/2017 | 12/29/2017 | 12/29/2017 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey...rough ok to cover...p/s u/g new ok
|
Rough-In Permanent Service | 12/28/2017 | 12/28/2017 | 12/28/2017 | A | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey.... 1) service panelboard barriers need installed on all ungrounded conductors..408.3(A)(2) 2) uffer ground connection shall be made accessible..250.68(A) 3) wall space 2' or greater shall have an outlet..210.52(A)(2)...2 places marked
|
Issue PAID IN FULL permit | | | 12/28/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/28/2017 | | DONE |
|
|
|
This permit was created on the web by Neal Rumsey
|