Final | 1/23/2018 | 1/24/2018 | 1/24/2018 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Thomas wilson Stairs not set for final that intrude on work space clearences. Final ok
|
Rough-In Permanent Service | 1/8/2018 | 1/9/2018 | 1/9/2018 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Thomas wilson Door barricaded to not use at inspection time, p/s u/g rec ok
|
Rough-In Permanent Service | 1/5/2018 | 1/8/2018 | 1/8/2018 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Thomas wilson Future stair to back door will encroach on working clearences. 110.26 A1 and A2. Working space shall be 30in wide by 36in deep.
|
Issue PAID IN FULL permit | | | 1/5/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/5/2018 | | DONE |
|
|
|
This permit was created on the web by Thomas wilson
|