Final | 4/23/2018 | 4/24/2018 | 4/24/2018 | A | PASS |
James Ady
|
|
|
garage code 1905 Phone #: ###-#### Inspection requested via web by kevin blackmon Final ok
|
Rough-In Permanent Service | 1/24/2018 | 1/25/2018 | 1/25/2018 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by kevin blackmon Rough in ok cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 1/12/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/12/2018 | | DONE |
|
|
|
This permit was created on the web by kevin blackmon
|