ELE-Aging Inspection | 7/17/2020 | 7/17/2020 | 7/17/2020 | | PEND |
Daryl DeGrange
|
|
|
This permit is still open with the City of Boise. Please call 208 ###-#### with progress report or any questions. If your job is complete, Please schedule an final inspection online, pdsonline.cityofboise.org Thank You! David
|
ELE-Aging Inspection | 4/17/2020 | 4/17/2020 | 4/17/2020 | | DONE |
Daryl DeGrange
|
|
|
Pursuant of contacting aging permits applicants is on hold until required Social Distancing has been removed.
|
Final | 3/5/2019 | 3/5/2019 | 3/5/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by David Baker See RI
|
Electrical Rough-In | 3/5/2019 | 3/5/2019 | 3/5/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by David Baker Listing and disconnecing means confirmed. 300.3(A)- Single conductors shall be installed in a wiring method recognized in chapter 3 of NEC. 300.18- Raceways shall be installed in complete runs. Exposed single conductors feeding sign through EMT not terminated at sign, wire leaves conduit and enter unbushed opening.
|
(F) Reprint permit | | | 1/22/2018 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 1/18/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/18/2018 | | |
|
|
|
|