Final | 2/9/2018 | 2/9/2018 | 2/9/2018 | P | PASS |
Rock A. Hudson
|
|
|
Please contact Larren Novak for access Phone #: ###-#### Inspection requested via web by steve ragan Final ok
|
Final | 2/5/2018 | 2/5/2018 | 2/5/2018 | P | NH |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by steve ragan Unit locked, called contact Rick, mail box full, must recall when accessible.
|
Conference | 1/30/2018 | 2/1/2018 | 2/1/2018 | A | DONE |
Rock A. Hudson
|
|
|
Electrical consult Phone #: ###-#### Inspection requested via web by steve ragan Discussed corrections noted on last inspection. Move or suppy strain relief at cord terminations to each server not located under receptacle and connect cubicals with listed electrical devices built into cubical construction. Disreguard correction for 605.9 for free standing office furniture, these are tables with printer and computers sitting on top plugged into plug strips. As per Daryl DeGrange the intent of code is listed furniture with electrical built in and would apply to it's cord and plug connection.
|
Final | 1/29/2018 | 1/30/2018 | 1/30/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Please contact Larren Novak for access Phone #: ###-#### Inspection requested via web by steve ragan Receptacles installed for servers in ceiling of 2 different rooms. Receptacles also added for computer stations. Wiring for cubicals not in yet. 400.14- Receptacles located in ceiling for servers shall be located so pull at joints or terminals is eliminated. Receptacles located 5 to 6' off to side of equipment served. 605.9- Surge suppression plug strips shall be 12 guage min and max of 2' in length. Called to attach to BLD17-04188
|
Telephone call | | | 1/30/2018 | | DONE |
|
|
|
called to see ste 200 could be Ste 207-left message on office phone-
|
Final | 1/26/2018 | 1/29/2018 | 1/29/2018 | A | NH |
Rock A. Hudson
|
|
|
Please contact Larren Novak for access Phone #: ###-#### Inspection requested via web by steve ragan Called contact for access no answer left message.
|
Issue PAID IN FULL permit | | | 1/26/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/26/2018 | | DONE |
|
|
|
This permit was created on the web by steve ragan
|
First Notice | 2/9/2018 | 2/9/2018 | | | |
Rock A. Hudson
|
|
|
|