Description
New: Rough in 8 apartments and install 2 5 packs.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/2/20187/2/20187/2/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Ryan Wilson
Final ok
Final6/28/20186/29/20186/29/2018AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Ryan Wilson
Units locked, up entrance wet tile no access, garages locked. Recall when ready
Final6/20/20186/22/20186/22/2018AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Ryan Wilson
Label main disconnect for west meter pack, secure house panel cover with all screws, All garages no access to receptacles, AFCI will not hold in 102 bed, all front outdoor receptacles shall have GFCI protection, 101 locked no access, 205 shall have a receptacle adjacent to 2nd basin in main bathroom, 205 no access to 1 bed due to door stacked blocking opening, 203 bed receptacle blocked by barn door, 202 barn door not in to check access to receptacles, 201 is staged blocking access to misc receptacles, 201 has art work over panel, no access to roof to check RTUs.
Permanent Service3/16/20183/16/20183/16/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Ryan Wilson
Right side service p/s u/g n ok
Permanent Service3/15/20183/15/20183/15/2018PFAIL
DetailsRock A. Hudson
Please inspect the new 400amp disconnect and meter base for permanent service. Thank you Phone #: ###-#### Inspection requested via web by Ryan Wilson
250.24(A)(4)- The grounding electrode system shall be connected where the grounded service conductor terminates in the service disconnecting means.
250.24(A)(5)- The grounded conductor shall not be connected to non-current carrying metal parts on the load side of service disconnect.
250.110- Equipment fasted in place. Non-current carrying metal parts shall be connected to an equipment grounding conductor. In meter pack sub gear
Permanent Service3/7/20183/8/20183/8/2018PPASS
DetailsRock A. Hudson
Please inspect the meter pack on the left. Thanks Phone #: ###-#### Inspection requested via web by Ryan Wilson
Available fault current posted 9,987 amp on 10K reated mains.
Left service only p/s u/g n ok
Permanent Service3/5/20183/6/20183/5/2018PCANC
DetailsRock A. Hudson
Left 6 pack only please Phone #: ###-#### >> Inspection requested via web by Ryan Wilson Inspection cancelled from web by: Ryan Wilson
Permanent Service2/27/20182/28/20182/28/2018AFAIL
DetailsRock A. Hudson
Please inspect the meter base on the left. Phone #: ###-#### Inspection requested via web by Ryan Wilson
110.9- Equipment intended to interupt current at fault levels shall have an interupting rating at least equal to the current that is available at the line terminals of the equipment. 12,081 available and 10k rated main breakers.
Electrical Rough-In2/5/20182/6/20182/6/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Ryan Wilson
Service wall incomplete.
All units rough in ok cover
Permanent Service1/26/20181/29/20181/29/2018PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Ryan Wilson
110.24- Available fault current shall be posted on all services prior to inspection.
230.71- Shall not exceed 6 means of disconnecting service. Must check for firewall seperating building into 2 seperate 4 unit structures.
250.24- Service shall be connected to a grounding electrode system.
Issue PAID IN FULL permit  1/26/2018 DONE
Payment received via Govolutions
Application received  1/26/2018 DONE
This permit was created on the web by Ryan Wilson
First Notice7/2/20187/2/2018   
DetailsRock A. Hudson