Final | 4/11/2018 | 4/12/2018 | 4/12/2018 | A | PASS |
Mark Moncarr
|
|
|
Key in front outlet Phone #: ###-#### Inspection requested via web by TOM BICANDI Ok final.
|
Rough-In Permanent Service | 1/29/2018 | 1/30/2018 | 1/30/2018 | A | PASS |
Mark Moncarr
|
|
|
Inspection requested via web by TOM BICANDI p/s u/g n ok
|
Issue PAID IN FULL permit | | | 1/29/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/29/2018 | | DONE |
|
|
|
This permit was created on the web by TOM BICANDI
|