Permit Information
Permit NumberELE18-00413
StatusFinaled
Name ENERGY ENTERPRISE GROUP LLC
Site Address 702 W IDAHO ST Unit: STE 400
Project Name 
Customer Number683
ePlanReviewNo
Description
Alteration: Electrical for TI
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/29/20183/30/20183/30/2018APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Final ok
Final3/22/20183/22/20183/22/2018PPART
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Check furniture and panel schedule on final. TCO ok
Electrical Rough-In3/2/20183/5/20183/5/2018APASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Ceiling only ok to cover
Electrical Rough-In3/1/20183/2/20183/2/2018APART
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Boarders only due to existing floor boxes said to be abandoned with several open knockouts in them. They are spread through out entire ceiling.
Boarders only rough in ok cover.
Electrical Rough-In2/9/20182/9/20182/9/2018PPASS
DetailsRock A. Hudson
please inspect monitoring walls and rest room walls for approval to cover. contact person is Marcelo Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Rooms noted wall and hardlid rough in ok cover
Electrical Rough-In2/7/20182/8/20182/8/2018APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Except monitoring and bath rooms wall rough in ok cover
Conference2/1/20182/2/20182/2/2018ADONE
DetailsRock A. Hudson
am please Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Discussed the condition of existing ceiling area and conference areas. All unsupported raceways shall be removed or if remaining shall be supported as per NEC. Conference rooms, 1- 300 sq.ft. shall have 7 total receptacles with 1 located in floor, 2- 156 sq. ft. 4 total receptacles and no floor receptacle required. Existing light boxes located above grid shall have receptacle removed due to being used as a blank for box. Listed bland covers shall be installed. Exist flourescent luminares to be relocated near original location, shall provide support wires and support fixture whips longer than 6'.
Issue PAID IN FULL permit  2/1/2018 DONE
Payment received via Govolutions
Application received  2/1/2018 DONE
This permit was created on the web by Kerri Hamilton
First Notice3/30/20183/30/2018   
DetailsRock A. Hudson