Final | 7/30/2018 | 7/31/2018 | 7/31/2018 | A | PASS |
James Ady
|
|
|
Danny. Phone #: ###-#### Inspection requested via web by Sean DeLacy final ok
|
Electrical Rough-In | 5/15/2018 | 5/15/2018 | 5/15/2018 | P | PASS |
James Ady
|
|
|
Ceiling Cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Remaining ceiling in TI ok to cover
|
Electrical Rough-In | 5/14/2018 | 5/14/2018 | 5/14/2018 | P | PASS |
James Ady
|
|
|
Ceiling Cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen remaining offices, ceiling only ok to cover
|
Electrical Rough-In | 5/7/2018 | 5/7/2018 | 5/7/2018 | P | PASS |
Rock A. Hudson
|
|
|
Ceiling cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Grid as noted on contractor print rough in ok cover
|
Electrical Rough-In | 3/27/2018 | 3/28/2018 | 3/28/2018 | P | PASS |
Rock A. Hudson
|
|
|
Ceiling Cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen IT room hardlid only rough in ok cover
|
Electrical Rough-In | 3/27/2018 | 3/27/2018 | 3/27/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Ceiling Cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen 300.11- Luminaires shall be supported independant of ceiling support system unless manufacturers instructions state ceilling system can handle additional weight. 300.15- All wiring shall terminate in a box and shall be accessible. Conduit with wiring in it, Old disconnect and buried box on perimeter wall.
|
Electrical Rough-In | 2/22/2018 | 2/23/2018 | 2/23/2018 | P | PASS |
Eric Story
|
|
|
Wall Cover. Danny is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Walls in Conference rooms ok to cover
|
Electrical Rough-In | 2/9/2018 | 2/9/2018 | 2/9/2018 | A | PASS |
Rock A. Hudson
|
|
|
Wall cover. Danny is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen BLD17-03978 history shows plan review received prints 11-1-17, new code adopted 7-1-17 with 60 day grace period. All jobs with plan review complete after 9-1-17 shall comply with 2017 NEC. 210.71- Called contact Dan and left message to inform required floor receptacles and total room receptacle counts are required for this job. Wall rough in ok cover
|
Electrical Rough-In | 2/7/2018 | 2/7/2018 | 2/7/2018 | A | FAIL |
James Ady
|
|
|
Wall Cover. Danny is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen 300.4 F Cable ron within 1 1/4in from face of framing member shall be protected. ( All 2in studs with MC cable ran horizontle shall be nail plated
|
Issue PAID IN FULL permit | | | 2/7/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/7/2018 | | DONE |
|
|
|
This permit was created on the web by Buster Bowen
|