Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE18-00561
StatusFinaled
Name PRIORITY ELECTRIC
Site Address 1150 W MYRTLE ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Temporary Power Pole: Set temp power pole for trailer and building spider boxes.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice2/14/20182/14/20184/1/2018 DONE
DetailsJames Ady
This permit finaled on the web by Tom Jenkins
Temporary Service2/14/20182/14/20182/14/2018PPASS
DetailsJames Ady
Please make later in the afternoon if you can Phone #: ###-#### Inspection requested via web by Tom Jenkins t/s u/g n ok
Temporary Service2/13/20182/14/20182/14/2018AFAIL
DetailsRock A. Hudson
Inspect temp power pole. Located next to transformer on the North side of the site. Phone #: ###-#### Inspection requested via web by Tom Jenkins
210.21(B)(1)- A singe receptacle installed on a individual branch circuit shall not have a ampere rating less than that of the branch circuit. 30 amp single receptacle with 40 amp overcurrent protection.
590.6(B)- Receptacles for temp power other than 120 volt shall have GFCI protection.
Issue PAID IN FULL permit  2/12/2018 DONE
Payment received via Govolutions
Application received  2/12/2018 DONE
This permit was created on the web by Tom Jenkins