First Notice | 2/14/2018 | 2/14/2018 | 4/1/2018 | | DONE |
James Ady
|
|
|
This permit finaled on the web by Tom Jenkins
|
Temporary Service | 2/14/2018 | 2/14/2018 | 2/14/2018 | P | PASS |
James Ady
|
|
|
Please make later in the afternoon if you can Phone #: ###-#### Inspection requested via web by Tom Jenkins t/s u/g n ok
|
Temporary Service | 2/13/2018 | 2/14/2018 | 2/14/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Inspect temp power pole. Located next to transformer on the North side of the site. Phone #: ###-#### Inspection requested via web by Tom Jenkins 210.21(B)(1)- A singe receptacle installed on a individual branch circuit shall not have a ampere rating less than that of the branch circuit. 30 amp single receptacle with 40 amp overcurrent protection. 590.6(B)- Receptacles for temp power other than 120 volt shall have GFCI protection.
|
Issue PAID IN FULL permit | | | 2/12/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/12/2018 | | DONE |
|
|
|
This permit was created on the web by Tom Jenkins
|