Permit Information
Permit NumberELE18-00565
StatusFinaled
Name JES ELECTRIC
Site Address 1034 S LA POINTE ST
Project NameMadre Taco Restaurant
Customer Number2018-11
ePlanReviewNo
Description
Addition: Tenant Improvement To Accommodate New Restaurant All Wiring Service To Finish Fixtures Included
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/30/20183/30/20183/30/2018PPASS
DetailsEric Story
We Are Ready For Final, The Owners Are Trying To Get This Done So They Can Start Training And Opening. Its All Ready For Ya Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett
Card signed for perm occ, Final ok
Conference3/30/20183/30/20183/30/2018ADONE
DetailsEric Story
I Am Am Ready To Final Out This Job But, I Want To Give You Some Time To Look At Everything And Make Sure No Surprise Thanks So Much Dave Phone #: ###-#### Inspection requested via web by jason shifflett
Discussed requirements at whats needed for final and all checked out just fine.
Electrical Rough-In3/20/20183/20/20183/20/2018PPASS
DetailsEric Story
We Would Like To Get A Cover Inspection On The Drop Ceilings So They Can Cover Them Up And We Can Button Up Everthing For A Final Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett
Suspended ceilings only ok to cover
Permanent Service2/28/20182/28/20182/28/2018PPASS
DetailsEric Story
I Have The fault Current For The Service From Idaho Power The Highest Values Are As Follows Line To Line Is 7,735 Amps Line To Neutral Is 5.634 Amps Which Keeps Us Well Below The 20 K AIC rating Of The breakers. Ill Make Temp Labels This Morning And Order Permanents For Final Thanks dave Phone #: ###-#### Inspection requested via web by jason shifflett
p/s o/h n ok
Rough-In Permanent Service2/26/20182/27/20182/27/2018PCANC
DetailsEric Story
We Are Ready For Servuce And Cover On The Panel Walls Thanks Phone #: ###-#### Inspection requested via web by jason shifflett
Electrical Rough-In2/27/20182/27/20182/27/2018PPASS
DetailsEric Story
We Are Ready For Servuce And Cover On The Panel Walls Thanks Phone #: ###-#### Inspection requested via web by jason shifflett
Panel wall and adjacent wall only ok to cover
Permanent Service2/27/20182/27/20182/27/2018PFAIL
DetailsEric Story
We Are Ready For Servuce And Cover On The Panel Walls Thanks Phone #: ###-#### Inspection requested via web by jason shifflett
110.24 Available fault current calc required prior to being energized
Permanent Service2/26/20182/27/20182/26/2018ACANC
DetailsEric Story
We Need Permanent Service And The Grounding Looked At So Concrete Driveway Can Pour Thanks Dave Phone #: ###-#### >> Inspection requested via web by jason shifflett Inspection cancelled from web by: jason shifflett Inspection cancelled from web by: jason shifflett
Electrical Rough-In2/13/20182/14/20182/14/2018PPASS
DetailsEric Story
I Need A partial wall Inspection Its Ready Thanks Inspection requested via web by jason shifflett
Walls only ok to cover
Issue PAID IN FULL permit  2/13/2018 DONE
Payment received via Govolutions
Owner Supplied Equipment  2/13/2018  
Application received  2/13/2018 DONE
This permit was created on the web by jason shifflett
First Notice3/30/20183/30/2018   
DetailsEric Story