First Notice | 4/3/2018 | 4/3/2018 | 2/6/2019 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Samatha Solberg
|
Electrical Rough-In | 4/2/2018 | 4/3/2018 | 4/3/2018 | P | PASS |
Rock A. Hudson
|
|
|
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Corrections complete Thank you.
|
Final | 4/3/2018 | 4/3/2018 | 4/3/2018 | P | PASS |
Rock A. Hudson
|
|
|
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Final ok
|
Electrical Rough-In | 4/2/2018 | 4/4/2018 | 4/2/2018 | A | CANC |
Tom Saunders
|
|
|
Justin ###-#### Phone #: ###-#### >> Inspection requested via web by Samatha Solberg Inspection cancelled from web by: Samatha Solberg
|
Final | 4/2/2018 | 4/2/2018 | 4/2/2018 | P | FAIL |
Rock A. Hudson
|
|
|
2nd notice- Corrections from 2-13-18. 300.15- All wiring shall terminate in a box. Front sign wiring on roof. 330.30(B)- MC shall be secured with in 12" of a box. Under cabinet receptacles. 356.30- Non-metallic seal tight on east condensing unit shall be secured with in 12" of terminations. 404.8- Circuit directories shall be updated. Ensure all wiring not being used disconnected. 314.17(A)- All unused openings shall be closed by approved means. West condencing units removed. Open KOs. 406.6- Receptacles shall have proper covers installed. Back room receptacle recessed in wall with caulking as cover. 7 Working days to complete, will revisit 4-12-18. If not action has been taken a activity hold will be accessed to parcel and no work or inspections will be allowed once accessed. Manager scanned and forwarded to supervisor while 2nd correction delivered.
|
Final | 2/13/2018 | 2/13/2018 | 2/13/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg 300.15- All wiring shall terminate in a box. Roof old sign removed. Open wiring. 330.30(B)- MC shall be secured with in 12" of a box. UC receptacles. 356.30- Non-metallic seal tight on east condensing unit new, shall be secured with in 12" of terminations. 404.8- Circuit directories shall be updated. Ensure all unused circuits have been disconnected. 314.17(A)- All unused openings shall be closed. West condensing units removed. * Note from Fire Marshal on site states furnace shall be relocated with clearences as per manufacturers spec. BCC 4-05-32 Code violations not to be retained. As leaving noticed receptacle recessed in wall with out proper cover. Caulking around perimeter of receptacle.
|
Issue PAID IN FULL permit | | | 2/13/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/13/2018 | | DONE |
|
|
|
This permit was created on the web by Samatha Solberg
|