Final | 6/22/2018 | 6/25/2018 | 6/25/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by JENNY EMEL All receptacles in break area are GFCI protected, 4- 2 pole receptacles in lab not required to be GFCI protected due to not being used as a kitchen and not located with in 6' of a sink. Final ok
|
Electrical Rough-In | 5/23/2018 | 5/24/2018 | 5/24/2018 | A | PASS |
Rock A. Hudson
|
|
|
Rough in panel.
Contact Steve Nuxoll with questions
Thank you and have a nice day!! Phone #: ###-#### Inspection requested via web by JENNY EMEL Panel board rough in ok cover
|
Electrical Rough-In | 5/16/2018 | 5/17/2018 | 5/17/2018 | A | PASS |
Rock A. Hudson
|
|
|
Request is for ceiling inspection
Please contact Steve Nuxoll with any questions.
Thank you and have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL Entry and office grid, reception millwork Rough in ok cover. Discussed required clearances for transformer to wall, determined by manufacturers instructions if under 112KVA under 1000 volts. And system bonding jumper location for metallic raceway to be in transformer if equipment ground and system bonding present as per 450.10.
|
Electrical Rough-In | 3/5/2018 | 3/5/2018 | 3/5/2018 | P | PASS |
Eric Story
|
|
|
Please contact Steve Nuxoll with any questions.
Have a lovely afternoon! Phone #: ###-#### Inspection requested via web by JENNY EMEL Shower walls and ceilings only ok to cover
|
Electrical Rough-In | 2/28/2018 | 3/1/2018 | 3/1/2018 | A | PASS |
Rock A. Hudson
|
|
|
Contact Steve Nuxoll with any questions
Thank you and have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL 5 receptacles in each conference room minimum. Baths and shower rooms not ready, Rest of walls rough in ok cover.
|
Issue PAID IN FULL permit | | | 2/28/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/28/2018 | | DONE |
|
|
|
This permit was created on the web by JENNY EMEL
|
First Notice | 6/25/2018 | 6/25/2018 | | | |
Rock A. Hudson
|
|
|
|